{"id":"AIBD-0895","title":"EPA approved a neural-network emissions model at the Mahrt Paper Mill after its NOx output passed all three federal statistical tests","summary":"EPA found that a neural network's NOx estimates for a mill turbine passed all three federal statistical tests. It estimated that two such systems cost less than half as much as hardware monitors.","date_observed":"2006-04-05","date_basis":"source publication","date_precision":"day","benefit_status":"reported","source_collection":null,"source_entry":null,"account":"MeadWestvaco ran Pavilion Technologies' Software CEM on a 25 MW combustion turbine and a boiler at its Mahrt Mill in Cottonton, Alabama. The neural network estimates nitrogen oxide (NOx) emissions from the units' sensor readings. MeadWestvaco asked EPA to approve it as an alternative to continuous emission monitoring systems under 40 CFR Part 75. For the turbine, it supplied 889 operating hours of data paired with certified reference measurements. EPA found that the model's NOx output passed the correlation test, the F-test and the bias test. The oxygen output failed the correlation test, which EPA judged acceptable. The boiler model failed the bias test and must apply a bias adjustment factor. EPA granted final approval on 5 April 2006 and required monthly accuracy audits in the ozone season. The approval covers the turbine only when it burns natural gas without duct burners. EPA estimated that two such systems would cost less than half the cost of two continuous emission monitoring systems.","category":"aggregate result","unexpected":false,"purpose":"Pavilion Technologies built Software CEM to estimate NOx and oxygen emissions from a combustion unit's sensor readings with a neural network.","system":"Pavilion Technologies Software CEM predictive emission monitoring system (PEMS)","model_version":null,"developer":"Pavilion Technologies","deployer":"MeadWestvaco Coated Board, Inc. (Mahrt Mill)","location":"Cottonton, Alabama, United States","domain":"Air emissions monitoring","segment":null,"benefit_type":"Reduced Task Cost","work_activities":["4.A.1.b.3","4.A.1.a.2"],"taxonomy_note":null,"registry_ids":{},"ratings":[{"group":"organizational","depth":1,"reason":"EPA estimated that two such systems at the mill would cost less than half as much a year as two continuous emission monitoring systems."}],"ai_role":{"status":"assessed","statement":"EPA compared the model's hourly NOx estimates with reference measurements taken at the same time, which isolates the software's accuracy. EPA describes the system as neural network software trained on the unit's operating conditions. The cost comparison is EPA's estimate."},"evidence":[{"kind":"regulatory document","citation":"U.S. Environmental Protection Agency, Clean Air Markets Division. Final Approval of the Predictive Emission Monitoring Systems Installed on Units X022 and Z008 at the Mahrt Paper Mill (Facility ID (ORISPL) 54802). Letter to MeadWestvaco Coated Board, Inc., 5 April 2006, with Attachments A to C.","title":"Final Approval of the Predictive Emission Monitoring Systems Installed on Units X022 and Z008 at the Mahrt Paper Mill","url":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf","date":"2006-04-05","written_by":"independent","quote":"The PEMS NO x ppm, dry output passed all three statistics."}],"replication":{"produced_by":["The model estimated NOx from turbine sensor inputs such as gas flow, load and temperatures.","MeadWestvaco compared the model's hourly output with certified reference measurements over 889 operating hours."],"must_hold":["The unit's input parameters stay within the operating envelope on which the model was trained.","The mill runs monthly accuracy audits with a portable analyzer in the ozone season."],"echoes":[]},"paired_incident":null,"headline":"EPA approves *Software CEM* to monitor a paper mill turbine's NOx","metric":"less than half the cost","comparator":{"against":"Two continuous emission monitoring systems (CEMS), the next least costly option under EPA's cost model","before":"$125,400 a year for two CEMS","after":"approximately $51,700 a year for two PEMS with in-house audits","basis":"assumed","quote":"Thus, even with the additional RAA requirement, the estimated annual cost of operating and maintaining two PEMS at the Mahrt mill using trained in-house staff and a portable analyzer would be less than half the cost associated with CEMS.","url":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf"},"later":null,"value":{"amount":"$36,650","what":"Estimated yearly saving of two PEMS over two CEMS at the mill, even if outside contractors run the audits","who":"MeadWestvaco (Mahrt Mill)","estimate":true,"quote":"Even if outside contractors are used instead of in-house staff, the annual cost for two PEMS would be significantly less ($36,650 less) than the annual cost associated with two CEMS.","url":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf"},"developer_country":"United States","deployer_country":"United States","unrated_because":null,"brief_notes":null,"brief":null,"revisions":[{"date":"2026-10-31","change":"Added the record from the finding of the U.S. Environmental Protection Agency.","source":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf","editor":"AIBD"}],"confidence":"found","shade":"high","claim_status":"Found by a regulator","claim_basis":"Sources: one independent regulatory document. The cited evidence includes no independent study or report.","case_jurisdictions":["United States"],"profile":{"case_id":"AIBD-0895","catalog_version":"1.0.0","source_fingerprint":"c5255ece789274830d325b9d7691623a1df8ac764b9781870ebb8186c97686d1","collection_refs":[{"collection_id":"aibd","version":"2026-10-31"},{"collection_id":"querist","version":"2026-10-25"}],"source_ids":["AIBD-0895-source-0001"],"families":{"strategic assessments":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"Editorial assignment.","review_state":"not_assessed","coverage":"partial","record_ids":[]},"evaluations":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"Editorial assignment.","review_state":"not_assessed","coverage":"partial","record_ids":[]},"monetary observations":{"state":"value_present","value":{"kind":"text","text":"An existing source-stated monetary observation is present in the original value object."},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["value"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial","record_ids":["AIBD-0895-legacy-value"]},"institutional decisions":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"Editorial assignment.","review_state":"not_assessed","coverage":"partial","record_ids":[]}},"fields":{"actors[]":{"state":"value_present","value":{"kind":"record_fields","fields":{"developer":"Pavilion Technologies","deployer":"MeadWestvaco Coated Board, Inc. (Mahrt Mill)"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["developer","deployer"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"actors[].ownership_control":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"ai_contribution":{"state":"value_present","value":{"kind":"record_fields","fields":{"ai_role":{"status":"assessed","statement":"EPA compared the model's hourly NOx estimates with reference measurements taken at the same time, which isolates the software's accuracy. EPA describes the system as neural network software trained on the unit's operating conditions. The cost comparison is EPA's estimate."}}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["ai_role"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"ai_relationship":{"state":"value_present","value":{"kind":"record_fields","fields":{"category":"aggregate result","ai_role":{"status":"assessed","statement":"EPA compared the model's hourly NOx estimates with reference measurements taken at the same time, which isolates the software's accuracy. EPA describes the system as neural network software trained on the unit's operating conditions. The cost comparison is EPA's estimate."}}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["ai_role","category"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"assessments[].alternatives":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"assessments[].assessor_date":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"assessments[].depth":{"state":"value_present","value":{"kind":"record_fields","fields":{"ratings":[{"group":"organizational","depth":1,"reason":"EPA estimated that two such systems at the mill would cost less than half as much a year as two continuous emission monitoring systems."}]}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["ratings"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"assessments[].display_confidence":{"state":"value_present","value":{"kind":"structured","data":{"confidence":"high","evidence_word":"found","claim_status":"Found by a regulator","basis":"Sources: one independent regulatory document. The cited evidence includes no independent study or report.","interpretation":"Existing display rule preserved; the richer outcome-specific confidence question still needs review."}},"provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"assessments[].rationale":{"state":"value_present","value":{"kind":"record_fields","fields":{"ratings":[{"group":"organizational","depth":1,"reason":"EPA estimated that two such systems at the mill would cost less than half as much a year as two continuous emission monitoring systems."}]}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["ratings"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"assessments[].rubric_version":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"assessments[].status_basis":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"assessments[].target":{"state":"value_present","value":{"kind":"record_fields","fields":{"ratings":[{"group":"organizational","depth":1,"reason":"EPA estimated that two such systems at the mill would cost less than half as much a year as two continuous emission monitoring systems."}]}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["ratings"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"availability":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"brief":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"case_kind":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"case_links[]":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"claims[].evidence_links":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"claims[].evidence_strength":{"state":"value_present","value":{"kind":"structured","data":{"answer":"Found by a regulator. Sources: one independent regulatory document. The cited evidence includes no independent study or report.","evidence_word":"found","claim_status":"Found by a regulator"}},"provenance":{"kind":"source_review","basis":"Editorial assignment.","record_fields":["evidence"],"source_refs":["AIBD-0895-source-0001"],"reviewed_on":"2026-10-29"},"review_state":"reviewed","coverage":"complete","display":{"answer":"Found by a regulator. Sources: one independent regulatory document. The cited evidence includes no independent study or report.","inferred":false}},"claims[].missingness":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"claims[].proposition":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"cross_border_flows[]":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"decisions[].action_outcome":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"institutional decisions"},"decisions[].grounds":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"institutional decisions"},"decisions[].institution_task":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"institutional decisions"},"decisions[].success_criterion":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"institutional decisions"},"deployment_stage":{"state":"value_present","value":{"kind":"structured","data":{"classification":"routine use","answer":"The system was in routine use. The mill had used the software on the turbine since June 1998 to comply with federal emission standards.","scope":"The period and activity described in the case."}},"provenance":{"kind":"source_review","basis":"Editorial assignment.","record_fields":["account","evidence"],"source_refs":["AIBD-0895-source-0001"],"reviewed_on":"2026-10-29"},"review_state":"reviewed","coverage":"complete","display":{"answer":"The system was in routine use. The mill had used the software on the turbine since June 1998 to comply with federal emission standards.","inferred":false}},"economics[].amount":{"state":"value_present","value":{"kind":"record_fields","fields":{"value":{"amount":"$36,650","what":"Estimated yearly saving of two PEMS over two CEMS at the mill, even if outside contractors run the audits","who":"MeadWestvaco (Mahrt Mill)","estimate":true,"quote":"Even if outside contractors are used instead of in-house staff, the annual cost for two PEMS would be significantly less ($36,650 less) than the annual cost associated with two CEMS.","url":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf"}}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["value"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"economics[].costs[]":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"economics[].counterfactual":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"economics[].currency_price_basis":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"economics[].gross_net":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"economics[].measure_type":{"state":"value_present","value":{"kind":"record_fields","fields":{"value":{"amount":"$36,650","what":"Estimated yearly saving of two PEMS over two CEMS at the mill, even if outside contractors run the audits","who":"MeadWestvaco (Mahrt Mill)","estimate":true,"quote":"Even if outside contractors are used instead of in-house staff, the annual cost for two PEMS would be significantly less ($36,650 less) than the annual cost associated with two CEMS.","url":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf"}}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["value"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"economics[].period_unit":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"economics[].realization":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"economics[].recipient_payer":{"state":"value_present","value":{"kind":"record_fields","fields":{"value":{"amount":"$36,650","what":"Estimated yearly saving of two PEMS over two CEMS at the mill, even if outside contractors run the audits","who":"MeadWestvaco (Mahrt Mill)","estimate":true,"quote":"Even if outside contractors are used instead of in-house staff, the annual cost for two PEMS would be significantly less ($36,650 less) than the annual cost associated with two CEMS.","url":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf"}}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["value"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"economics[].return_payback":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"economics[].valuation_method":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"evaluations[].ai_uplift":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].comparator":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].design":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].effect":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].exposure":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].id":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].measurement_method":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].metric":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].reproduction_materials":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].setting_sample":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"evaluations[].uncertainty_limitations":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"evaluations"},"external_references[]":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"follow_up[]":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"human_oversight":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"id":{"state":"value_present","value":{"kind":"record_fields","fields":{"id":"AIBD-0895"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["id"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"infrastructure_dependencies[]":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"outcomes[].beneficiaries":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"outcomes[].beneficiary_count":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"outcomes[].benefit_type":{"state":"value_present","value":{"kind":"record_fields","fields":{"benefit_type":"Reduced Task Cost"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["benefit_type"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"outcomes[].claim":{"state":"value_present","value":{"kind":"record_fields","fields":{"account":"MeadWestvaco ran Pavilion Technologies' Software CEM on a 25 MW combustion turbine and a boiler at its Mahrt Mill in Cottonton, Alabama. The neural network estimates nitrogen oxide (NOx) emissions from the units' sensor readings. MeadWestvaco asked EPA to approve it as an alternative to continuous emission monitoring systems under 40 CFR Part 75. For the turbine, it supplied 889 operating hours of data paired with certified reference measurements. EPA found that the model's NOx output passed the correlation test, the F-test and the bias test. The oxygen output failed the correlation test, which EPA judged acceptable. The boiler model failed the bias test and must apply a bias adjustment factor. EPA granted final approval on 5 April 2006 and required monthly accuracy audits in the ozone season. The approval covers the turbine only when it burns natural gas without duct burners. EPA estimated that two such systems would cost less than half the cost of two continuous emission monitoring systems.","benefit_type":"Reduced Task Cost"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["account","benefit_type"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"outcomes[].distribution":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"outcomes[].duration":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"outcomes[].id":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"outcomes[].stakeholder_group":{"state":"value_present","value":{"kind":"record_fields","fields":{"ratings":[{"group":"organizational","depth":1,"reason":"EPA estimated that two such systems at the mill would cost less than half as much a year as two continuous emission monitoring systems."}]}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["ratings"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"outcomes[].status":{"state":"value_present","value":{"kind":"record_fields","fields":{"benefit_status":"reported"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["benefit_status"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"outcomes[].tradeoffs":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"outcomes[].unexpected":{"state":"value_present","value":{"kind":"record_fields","fields":{"unexpected":false,"purpose":"Pavilion Technologies built Software CEM to estimate NOx and oxygen emissions from a combustion unit's sensor readings with a neural network."}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["unexpected","purpose"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"places[]":{"state":"value_present","value":{"kind":"record_fields","fields":{"location":"Cottonton, Alabama, United States","developer_country":"United States","deployer_country":"United States"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["location","developer_country","deployer_country"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"purpose":{"state":"value_present","value":{"kind":"record_fields","fields":{"purpose":"Pavilion Technologies built Software CEM to estimate NOx and oxygen emissions from a combustion unit's sensor readings with a neural network."}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["purpose"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"record_dates":{"state":"value_present","value":{"kind":"record_fields","fields":{"date_observed":"2006-04-05","date_basis":"source publication","date_precision":"day","revisions":[{"date":"2026-10-31","change":"Added the record from the finding of the U.S. Environmental Protection Agency.","source":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf","editor":"AIBD"}]}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["date_observed","date_basis","date_precision","revisions"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"replication.attempts[]":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"replication.conditions":{"state":"value_present","value":{"kind":"record_fields","fields":{"replication":{"produced_by":["The model estimated NOx from turbine sensor inputs such as gas flow, load and temperatures.","MeadWestvaco compared the model's hourly output with certified reference measurements over 889 operating hours."],"must_hold":["The unit's input parameters stay within the operating envelope on which the model was trained.","The mill runs monthly accuracy audits with a portable analyzer in the ozone season."],"echoes":[]}}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["replication"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"revision_history[]":{"state":"value_present","value":{"kind":"record_fields","fields":{"revisions":[{"date":"2026-10-31","change":"Added the record from the finding of the U.S. Environmental Protection Agency.","source":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf","editor":"AIBD"}]}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["revisions"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"sector":{"state":"value_present","value":{"kind":"record_fields","fields":{"domain":"Air emissions monitoring"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["domain"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"sources[].access_version":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"sources[].citation_locator":{"state":"value_present","value":{"kind":"record_fields","fields":{"evidence":[{"kind":"regulatory document","citation":"U.S. Environmental Protection Agency, Clean Air Markets Division. Final Approval of the Predictive Emission Monitoring Systems Installed on Units X022 and Z008 at the Mahrt Paper Mill (Facility ID (ORISPL) 54802). Letter to MeadWestvaco Coated Board, Inc., 5 April 2006, with Attachments A to C.","title":"Final Approval of the Predictive Emission Monitoring Systems Installed on Units X022 and Z008 at the Mahrt Paper Mill","url":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf","date":"2006-04-05","written_by":"independent","quote":"The PEMS NO x ppm, dry output passed all three statistics."}]}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["evidence"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"sources[].id":{"state":"value_present","value":{"kind":"identifiers","identifiers":["AIBD-0895-source-0001"],"role":"Existing evidence items, in their original order"},"provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"review_state":"record_mapped","coverage":"complete"},"sources[].language":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"sources[].relationship":{"state":"value_present","value":{"kind":"record_fields","fields":{"evidence":[{"kind":"regulatory document","citation":"U.S. Environmental Protection Agency, Clean Air Markets Division. Final Approval of the Predictive Emission Monitoring Systems Installed on Units X022 and Z008 at the Mahrt Paper Mill (Facility ID (ORISPL) 54802). Letter to MeadWestvaco Coated Board, Inc., 5 April 2006, with Attachments A to C.","title":"Final Approval of the Predictive Emission Monitoring Systems Installed on Units X022 and Z008 at the Mahrt Paper Mill","url":"https://www.epa.gov/sites/default/files/2015-05/documents/meadwestvaco_coated_board_inc.pdf","date":"2006-04-05","written_by":"independent","quote":"The PEMS NO x ppm, dry output passed all three statistics."}]}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["evidence"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"sources[].upstream_sources":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"strategic_assessments[]":{"state":"unresolved","review_state":"not_assessed","coverage":"partial","family":"strategic assessments"},"summary":{"state":"value_present","value":{"kind":"record_fields","fields":{"summary":"EPA found that a neural network's NOx estimates for a mill turbine passed all three federal statistical tests. It estimated that two such systems cost less than half as much as hardware monitors.","account":"MeadWestvaco ran Pavilion Technologies' Software CEM on a 25 MW combustion turbine and a boiler at its Mahrt Mill in Cottonton, Alabama. The neural network estimates nitrogen oxide (NOx) emissions from the units' sensor readings. MeadWestvaco asked EPA to approve it as an alternative to continuous emission monitoring systems under 40 CFR Part 75. For the turbine, it supplied 889 operating hours of data paired with certified reference measurements. EPA found that the model's NOx output passed the correlation test, the F-test and the bias test. The oxygen output failed the correlation test, which EPA judged acceptable. The boiler model failed the bias test and must apply a bias adjustment factor. EPA granted final approval on 5 April 2006 and required monthly accuracy audits in the ozone season. The approval covers the turbine only when it burns natural gas without duct burners. EPA estimated that two such systems would cost less than half the cost of two continuous emission monitoring systems."}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["summary","account"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"systems[].autonomy_permissions":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"systems[].component_role":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"systems[].deployment_configuration":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"systems[].inputs_outputs":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"systems[].model_name":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"systems[].model_version":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"systems[].product_name":{"state":"value_present","value":{"kind":"record_fields","fields":{"system":"Pavilion Technologies Software CEM predictive emission monitoring system (PEMS)"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["system"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"systems[].provider":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"taxonomy_crosswalks[]":{"state":"unresolved","provenance":{"kind":"curatorial","basis":"Editorial assignment.","record_fields":[],"source_refs":[]},"reason":"This is an explicit unresolved assignment: the sources on record do not settle this question.","review_state":"not_assessed","coverage":"partial"},"title":{"state":"value_present","value":{"kind":"record_fields","fields":{"title":"EPA approved a neural-network emissions model at the Mahrt Paper Mill after its NOx output passed all three federal statistical tests","headline":"EPA approves *Software CEM* to monitor a paper mill turbine's NOx"}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["title","headline"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"},"version":{"state":"value_present","value":{"kind":"identifiers","identifiers":["5013394ad9d72b53e47012c52b029721e0b67820a8c0e8407d720eb0ec147610"],"role":"SHA-256 of the complete public record and its assessments"},"provenance":{"kind":"curatorial","basis":"SHA-256 of the public record, its assessments, and its displayed answers and notes, excluding its own identifier and the derived coverage summary.","record_fields":[],"source_refs":[]},"review_state":"record_mapped","coverage":"complete"},"workflow":{"state":"value_present","value":{"kind":"record_fields","fields":{"account":"MeadWestvaco ran Pavilion Technologies' Software CEM on a 25 MW combustion turbine and a boiler at its Mahrt Mill in Cottonton, Alabama. The neural network estimates nitrogen oxide (NOx) emissions from the units' sensor readings. MeadWestvaco asked EPA to approve it as an alternative to continuous emission monitoring systems under 40 CFR Part 75. For the turbine, it supplied 889 operating hours of data paired with certified reference measurements. EPA found that the model's NOx output passed the correlation test, the F-test and the bias test. The oxygen output failed the correlation test, which EPA judged acceptable. The boiler model failed the bias test and must apply a bias adjustment factor. EPA granted final approval on 5 April 2006 and required monthly accuracy audits in the ozone season. The approval covers the turbine only when it burns natural gas without duct burners. EPA estimated that two such systems would cost less than half the cost of two continuous emission monitoring systems.","replication":{"produced_by":["The model estimated NOx from turbine sensor inputs such as gas flow, load and temperatures.","MeadWestvaco compared the model's hourly output with certified reference measurements over 889 operating hours."],"must_hold":["The unit's input parameters stay within the operating envelope on which the model was trained.","The mill runs monthly accuracy audits with a portable analyzer in the ozone season."],"echoes":[]}}},"provenance":{"kind":"legacy_record","basis":"Editorial assignment.","record_fields":["account","replication"],"source_refs":[]},"review_state":"record_mapped","coverage":"partial"}},"summary":{"total":91,"addressed":91,"known":32,"reviewed":2,"reviewed_complete":2,"reviewed_partial":0,"record_mapped":30,"review_not_assessed":59,"not_assessed":0,"complete":false,"by_state":{"value_present":32,"not_reported":0,"unresolved":59,"not_assessed":0,"not_applicable":0,"withheld":0,"source_unavailable":0}}},"presentation_version":"ad1324df9996097f36134072bfc936cd2d5a4032df038e5d6eff459fb9a4acff"}